Parts of PS
index > DC Power > Parts of PS

JYM-I insulation monitor

editor:admin    date:2014-07-22

 

The insulation monitor is used to monitor insulation condition of the buses and branch circuits. In normal condition, the insulation monitor detects the bus voltage and calculates the insulation resistance of bus vs. ground through the bus voltage. When the insulation resistance is lower than the alarm setting, the insulation monitor will check all the branch circuits in turn to detect the branch circuits with degraded insulation and calculate the insulation resistance, and generate alarm via the LED indicators on the panel. In the meantime, the alarm information is sent to the PCU for display.
Specifications
See Table JYM-I-1 & Table JYM-I-2 for the major technical specifications of Emerson JYM-1 insulation monitor.
Table JYM-I-1  Technical conditions

No.
Item
Technical conditions
1
Ambient temperature
-5~+40 ℃
2
Relative humidity
≤90%
3
Power supply
DC 80~320V
4
Power consumption
≤70W
5
Weight
 

Table JYM-I-2  Specifications

SN.
Item
Specification
1
Voltage measurement accuracy (±1V DC~±300V DC)
1.5%(typical 1%)
2
Setting range of insulation resistance of circuit branch
500Ω~50KΩ(default 20KΩ)
3
The number of additional slave units
No more than 4
4
The number of branches to be monitored
No more than 240
5
Measurement accurancy of insulation resistance of branches
20%(typical 10%)
6
Detection time of each branch
3~6s
7
Amplitude and frequency of low frequency signal
About 4V, 10±0.1Hz
8
Communication interface
RS485
9
Alarm point hysteresis
40%