No.
|
Item
|
Technical conditions
|
1
|
Ambient temperature
|
-5~+40 ℃
|
2
|
Relative humidity
|
≤90%
|
3
|
Power supply
|
DC 80~320V
|
4
|
Power consumption
|
≤70W
|
5
|
Weight
|
|
SN.
|
Item
|
Specification
|
1
|
Voltage measurement accuracy (±1V DC~±300V DC)
|
1.5%(typical 1%)
|
2
|
Setting range of insulation resistance of circuit branch
|
500Ω~50KΩ(default 20KΩ)
|
3
|
The number of additional slave units
|
No more than 4
|
4
|
The number of branches to be monitored
|
No more than 240
|
5
|
Measurement accurancy of insulation resistance of branches
|
20%(typical 10%)
|
6
|
Detection time of each branch
|
3~6s
|
7
|
Amplitude and frequency of low frequency signal
|
About 4V, 10±0.1Hz
|
8
|
Communication interface
|
RS485
|
9
|
Alarm point hysteresis
|
40%
|