Introduction
SN
|
Name
|
Quantity
|
Input range
|
Display range
|
Error*
|
Remark
|
1
|
AC voltage
|
1
|
0 ~ 2Vac standard signal
|
0 ~ 500V
|
± 2% rated value
|
Used with Emerson AC voltage sampling board (AVSB) A14A3S1
|
2
|
Bus voltage
|
1
|
0 ~ 320Vdc
|
0 ~ 320V
|
± 0.5% rated value
|
|
3
|
Battery string voltage
|
1
|
0 ~ 320Vdc
|
0 ~ 320V
|
± 0.5% rated value
|
|
4
|
Load current
|
1
|
0 ~ 75mVdc
|
0 ~ 1500A
|
± 0.5% rated value
|
Used with shunt
|
5
|
Battery current
|
1
|
-75mVdc ~ +75mVdc
|
-1500A ~ +1500A
|
± 0.5% rated value
|
|
6
|
Battery ambient temperature
|
1
|
250uA ~ 330uA current
|
-15°C ~ +50°C
|
± 2°C
|
Used with Emerson temperature sensor
|
7
|
Positive bus -/ netagtive bus - ground voltage
|
1
|
0 ~ 320Vdc
|
0 ~ 320Vdc
|
± 2% rated value
|
Should use the inbuilt insulation detection function of PSM-E01 PCU
|
*: Sampling error of PSM-E01 PCU only excluding the error of transducer or AVSB
|
SN
|
Name
|
Status
|
Features
|
Remark
|
1
|
Output air breaker status
|
NC
|
All signals are series connected and input to PCU as one signal
|
Close: the signal has 12V voltage
Open: the signal has 0V voltage.
NC or NO can be set in PCU
|
2
|
Battery fuse status
|
NC
|
For detecting battery fuse blown status
|
|
3
|
Insulation relay status
|
NO
|
For detecting the insulation status of DC bus through insluation relay
|
|
4
|
AC air breaker trip signal
|
NC
|
The status or tripping signal of AC air breaker of EP system
|
|
5
|
Battery cell abnormal signal
|
NC
|
Battery string and cell status sent from battery detector
|
|
6
|
SPD fault signal
|
NC
|
Class C SPD status of EP system
|
SN
|
Name
|
Quantity
|
Remark
|
1
|
Audible alarm signal
|
1
|
12Vdc drive voltage. Piezoelectricity ceramic buzzer with 12V voltage is recommended
|
2
|
Alarm indicator signal
|
1
|
12Vdc drive voltage. Yellow LED indicator is recommended
|
3
|
Alarm relay output signal
|
1
|
Contact capacity: 220Vdc/300mA, 250Vac/1A. All alarms output through one relay
|
4
|
Serial port
|
2
|
The PCU has RS232 and RS485 ports, but they cannot be used at the same time. All analog signals and digital signals can be sent to a host through these ports with Modbus or CDT91 protocol
|
SN
|
Name
|
Content
|
Remark
|
1
|
Battery management
|
According to the preset parameters, manage battery boost charging (BC) & float charging (FC), current-limit charging, temperature compensation and battery capacity test
|
At most 48 hours of manual BC operating is allowed
|
2
|
Battery BC protection
|
Perform battery BC protection according to the preset auto BC protection time
|
The manual BC protection time and auto BC protection time are two different parameters. Set them separately
|
Switch to FC upon system abnormality
|
|
||
3
|
Alarming
|
Battery shunt disconnection, load shunt disconnection
|
The shunt is damaged or the cable is disconnected
|
Battery fuse blown, AC air breaker trip, output air breaker trip, SPD fault, battery cell abnormal
|
|
||
Bus insulation deterioration
|
This alarm indicates that the insulation relay has alarm if the insulation detecting mode is set to “Extn” or that the difference between the positive bus to ground voltage and negative bus to ground voltage exceeds threshold if the mode is set to “Intn”
|
||
AC over-/under-voltage, AC input failure alarm (AC voltage <50V)
|
|
||
Bus, battery over-/under-voltage alarm
|
|
||
Battery charge over current alarm
|
|
||
System current imbalance alarm
|
The difference between load current plus battery current and the output current sum of all rectifiers exceeds threshold
|
||
Battery string temperature abnormal alarm
|
Alarm occurs when the battery temperature exceeds the range of -15ºC ~ 45ºC. Battery temperature compensation will stop
|
||
Rectifier protection, fault, communication interruption alarm
|
|
||
PCU malfunction
|
The internal 12V and 5V power supplies of PCU are abnormal
|
||
4
|
Background communication
|
PCU communicates with the host through RS232/RS485 mode. The protocol is Modbus or CDT91 (settable)
|
www.emerson-cn-com
|