Item
|
Specifications
|
Input voltage
|
323V~475V (three-phase three-wire)
|
Input current
|
£4A
|
AC input frequency
|
50Hz±10%
|
Efficiency
|
³90%
|
Item
|
Specifications
|
Remarks
|
Output voltage range
|
198~286V
|
220V series
|
Output current
|
Rated output: 5A
|
The maximal output is 105%~110% of the rated value.
|
Voltage rise time
|
3~10 seconds
|
Soft startup time
|
Range of the output constant current
|
10%~110%
|
|
Precision of the stabilized current
|
£±1%
|
20% current limit test
|
Ripple coefficient of the output voltage
|
£0.1%
|
|
Precision of the stabilized voltage
|
£±0.5%
|
|
Temperature coefficient (1/℃)
|
£0.02%
|
|
Item
|
Specifications
|
Remarks
|
Short circuit foldback of output
|
Foldback current £40% rated current, automatic recoverable
|
|
Protection of the output overvoltage
|
293±6VDC, unrecoverable and to be powered on again and restarted
|
No DC output after the protection
|
Alarm for the output undervoltage
|
191 ± 6VDC recoverable
|
DC output available after alarming
|
Protection of the input overvoltage
|
482 ±6VAC, recoverable with the recovery point of 460 ±15VAC
|
No DC output after the protection
|
Protection of the input undervoltage
|
316 ±6VAC, recoverable with the recovery point of 335 ±10VAC
|
No DC output after the protection
|
Phase failure protection
|
Recoverable
|
No DC output after the protection
|
Over-temperature protection
|
Over-temperature protection point: 85 ℃; Recovery point: 75 ℃.
|
Accuracy: ± 5 ℃
|
Fan temperature control
|
Fan start point: 50℃; Fan stop point: 38℃
|
Accuracy: ± 5℃
|
No.
|
Item
|
Specifications
|
Remarks
|
1
|
Remotely acquiring alarm/digital signal
|
Transmit to the PCU the protection signals such as the AC overvoltage/ undervoltage, Phase failure, output overvoltage/undervoltage and rectifier overtemperature, and the fault signals of the rectifier.
|
|
2
|
Remotely acquiring analog signal
|
Measure the output voltage and current of the rectifier, and send them to the LED of rectifier for display and report to the PCU.
|
|
3
|
Remotely controling system state
|
Based on the commands of the PCU, control the on/off and boost/float charging of the rectifier.
|
The manual control is also furnished to shield the control of the PCU.
|
4
|
Remotely adjusting voltage analog signal
|
Based on the commands of the PCU, regulate the output voltage of the rectifier.
|
|
Based on the commands of the PCU, regulate the output current limiting threshold of the rectifier within the range of 10%~100%.
|
|||
5
|
Display
|
The LED of the rectifier, which displays the output current and voltage of the rectifier, are under the control of the monitoring board in the rectifier.
|
|