Rectifier
|
Output
|
HD22005-2
|
220V/5A
|
HD11010-2
|
110V/10A
|
Item
|
Specifications
|
Voltage
|
323V~475V(3-phase 3-line system)
|
Current
|
HD22005-2≦4A HD11010-2≦4A
|
Frequency
|
50Hz±10%
|
Power factor
|
≧0.92
|
Efficiency
|
≧94%
|
Item
|
Specifications
|
Remark
|
||
Output voltage
|
198~286V(220V series )
|
99~143V(110V series )
|
|
|
Output current
|
HD22005-2: rated output 5A
|
HD11010-2: rated output 10A
|
Max output: 105%~110% of rated value
|
|
Voltage rise time
|
3~8 seconds
|
Soft start time
|
||
Range of output constant current
|
10%~100%
|
|
||
Accuracy of current stabilization
|
≦±1%
|
|
||
Ripple coefficient of load voltage
|
≦0.03%
|
≦0.05%
|
|
|
Accuracy of voltage stablization
|
≦±0.5%
|
|
||
Temperature coefficient (1/℃)
|
≦0.2‰
|
|
Item
|
Specifications
|
Remark
|
|
Output foldback on short-circuit
|
Foldback current ≤40% rated current, recoverable
|
|
|
Output overvoltage protection point
|
220V series : 291±4VDC
|
110V series : 145±2VDC
|
Variable through the PCU
|
Output undervoltage alarm point
|
220V series : 194 ±4VDC
|
110V series : 97±2VDC
|
|
Input overvoltage protection point
|
480 ±5VAC, recoverable, hysteresis 5~15V
|
|
|
Input undervoltage protection point
|
318 ±5VAC, recoverable, hysteresis 10~20V
|
|
|
Phase-failure protection
|
Recoverable
|
|
|
Over-temperature protection
|
Overheat protection point: 85℃, recovable after cooling down
|
Accuracy: ±5℃
|
No
|
Item
|
Specifications
|
Remark
|
1
|
Remote signalling
|
Transmit the protection and fault signals of the rectifier (including signlas of AC overvoltage/undervoltage, phase-failure, output overvoltage/undervoltage, and over-temperature) to the PCU.
|
|
2
|
Remote measuring
|
Measure the output voltage and current of the rectifier, and then send them to local LED and the PCU.
|
|
3
|
Remote control
|
Switch on/off the rectifier or change over charge modes between equalize and float according to the commands from the PCU.
|
The user can also disable the commands from the PCU manually.
|
4
|
Remote adjustment
|
Adjust the output voltage of the rectifier according to the commands from the PCU.
|
|
Adjust the output current limit point of the rectifier within the range of 10%~100% according to the commands from the PCU.
|
|||
5
|
Display
|
Control local LED to display the output current and voltage of the rectifier.
|
|